5925--Newington Replacement Breakers 36C24125Q0602

Solicitation 36C24125Q0602 Copied Notice ID 2a3da0ef562046b481f4fb0d4ceb6d69 Copied VETERANS AFFAIRS, DEPARTMENT OF — 241-NETWORK CONTRACT OFFICE 01 (36C241)
SAM.gov
Posted
Jul 02, 2025
Deadline
Jul 15, 2025
Set-aside
VSA
NAICS
811210
PSC
5925

Summary

AI-generated · Aug 27, 2025

Replace and refurbish one molded-case circuit breaker at the VA Medical Center Newington. The work includes testing, inspecting, and replacing the breaker case and the associated trip unit, with a single line-item quote request for the replacement package (breaker case and trip unit). The procurement is set aside for Veteran-Owned Small Businesses, and quotes are requested through an RFQ process rather than a separate solicitation document.

A subsequent Q&A clarifies that two breakers are involved: the first breaker must be replaced because the support bracket is damaged and cannot be racked out; it uses Eaton MDN4083XEA0552N (K600-AR-600NM frame, 480V, Digitrip 520, 250A trip). The second breaker also requires its trip unit replacement and will need a temporary unit to keep CT scanners operational until the trip unit is rebuilt, as downtime is not acceptable. Each breaker must include a testing report via secondary injection testing to verify functionality; additional information (catalog numbers and photos) may be requested.

Description This is a combined synopsis/solicitation for commercial products and commercial services prepared in accordance with the format in Federal Acquisition Regulation (FAR) subpart 12.6, Streamlined Procedures for Evaluation and Solicitation for Commercial Products and Commercial Services, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation document will not be issued. This solicitation is issued as an RFQ. The solicitation document and incorporated provisions and clauses are those in effect through Federal Acquisition Circular FAC 2025-04; May 12, 2025. This solicitation is set-aside for VOSB competition. The associated North American Industrial Classification System (NAICS) code for this procurement is 811210, Electronic and Precision Equipment Repair and Maintenance, with a small business size standard of $34 Million. The FSC/PSC is J059, Maintenance, Repair and Rebuilding of Equipment Electrical and Electronic Equipment Components The VA Medical Center Newington, 555 Willard Ave, Newington CT 06111 is seeking a Vendor to Test, Inspect and replace 1 molded case breaker and the refurbishment of 1 breaker trip unit. All interested companies shall provide quotations for the following: Supplies/Services Line Item Description Quantity Unit of Measure Unit Price Total Price 0001 Breaker Case and Trip unit replacement 1 JB

From Combined Synopsis/Solicitation posted on Jul 02, 2025

36C241-25-AP-4384 Newington Replacement Breakers Q and A Can you please advise part # of breaker needed / pictures of existing breaker? There are 2 breakers noted in the solicitation. The first of which cannot be racked out for information due to the support bracket being damaged. This is the breaker that needs to be replaced. Here is the information I have available to me: MFR: EATON Catalog # MDN4083XEA0552N Frame Type: K600-AR-600NM Frame Size: 800 Voltage Rating: 480 Trip Unit: DIGITRIP 520 Trip Rating: 250 Can you please send us the catalog number for this breaker and information on the trip unit? If you have any pictures, that would help. The second breaker failed a trip test and will need the trip unit replaced. Here is the information I have available from the second breaker. MFR: EATON Catalog # MDN4083XEA0552N Frame Type: K600-AR-600NM Frame Size: 800 Voltage Rating: 480 Trip Unit: DIGITRIP 520 Trip Rating: NA (This will need to be dialed in as best you can) Please note as stated in the SOW, this breaker will need a temporary unit for use until the trip unit is rebuilt, and the breaker can be racked back in. This unit supports the hospital s CT scanners and downtime is not acceptable. Please also note that each breaker will require a testing report via secondary injection testing to verify functionality.

From Combined Synopsis/Solicitation posted on Aug 18, 2025

Notice history

2
  1. Combined Synopsis/Solicitation Posted Jul 02, 2025
  2. Combined Synopsis/Solicitation LATEST Posted Aug 18, 2025
    • Title: 5925--Newington Replacement BreakersJ059--Newington Replacement Breakers
    • Description: Description was updated
    • Response Deadline: Jul 15, 2025Aug 25, 2025

Details

Solicitation number 36C24125Q0602
Notice ID 2a3da0ef562046b481f4fb0d4ceb6d69
Notice type Combined Synopsis/Solicitation
Product / Service (PSC) 5925
NAICS 811210
Set-aside Veteran Set Aside
Place of performance Newington, CT
Archive date Sep 13, 2025

Award Information

Awardees
0

Documents

1
View on SAM.gov

Contacts

primary
Shawn Lawrence

Contract Specialist

Email

Phone

Agency

VETERANS AFFAIRS, DEPARTMENT OF
VETERANS AFFAIRS, DEPARTMENT OF
241-NETWORK CONTRACT OFFICE 01 (36C241)

Place of Performance

VA Medical Center Newington
555 Willard Ave
Newington, CT 06111

Dates

Posted Jul 02, 2025 1 year ago
Last Updated Aug 06, 2026 1 day ago
Due Jul 15, 2025 1 year ago