Contacts, documents and full notice history are available with a subscription.
Sources Sought VSA Expired 1 notice 1 document

Z2DZ--Bolt Replacement Survey ASTM A307 36C25926Q0034

Solicitation 36C25926Q0034 Copied Notice ID bb11692517d4478bb526158662e91625 Copied VETERANS AFFAIRS, DEPARTMENT OF — NETWORK CONTRACT OFFICE 19 (36C259)
SAM.gov
Posted
Oct 17, 2025
Deadline
Oct 24, 2025
Set-aside
VSA
NAICS
236220
PSC
Z2DZ

Summary

AI-generated · Oct 18, 2025

Survey and identify all ASTM A307 bolts installed on high- and medium-pressure steam and hot-water piping (over 50 psi) at a VA medical facility in Oklahoma City, and develop a plan to replace them with ASTM A193 bolts suitable for steam/hot-water service. The contractor must verify all information on-site, assess current conditions, perform measurements, and supply new materials as required. All work must comply with VA, federal, state, and local laws and safety policies; the campus is tobacco-free and subcontractors must also comply.

Inspect specified areas including multiple mechanical rooms and the central boiler plant to locate ASTM A307 bolts, document quantities by equipment, and cut/remove insulation from flanges to access bolts as needed. Prioritize the replacement plan for high- and medium-pressure piping and deliver a report detailing bolt locations and counts. This is an information-only request for sources of interest, with no award associated with this notice. If interested, provide your company size, SAM UEI, and whether you have an FSS/GSA contract (including contract number if applicable).

Oklahoma City Veterans Affairs Health Care System ASTM307 Bolt Replacement Survey I. GENERAL: This project is to survey and identify locations of ASTM 307 bolts and develop a replacement plan to replace the bolts with the required ASTM A193 at the OKC VA HCS at Oklahoma City, Oklahoma. The contractor is fully responsible for verifying and validating all information contained within this statement of work. Contractor must fully evaluate the condition of the existing structures and verify the current condition of the project site. All measurements/quantities provided in this document are approximate and are to be used for reference only. The contractor will be responsible for taking on-site measurements and verifying all quantities and distances. All materials/fasteners/etc. must be new and provided by the contractor unless otherwise specified. The contractor shall abide by all Safety, Security and Infection Control Policies and Procedures of the Oklahoma City VA HCS. VA facilities are tobacco free. No smoking is permitted on VA property. The contractor is responsible for their subcontractor s compliance with this policy. All work must conform to, and comply with, the latest edition/version of ALL applicable VA, federal, state, and local laws, rules, regulations, codes, and standards. II. JUSTIFICATION: Per VHA directive, All VAMCs must complete a survey of their existing steam and hot water piping systems and develop a replacement plan, prioritizing high and medium pressure steam and hot water piping systems operating at over 50 pounds per square inch. If ASTM A307 bolts (all grades) are identified, an Interim Safety Measure must be developed to ensure the safety of staff and the facility until replacement is complete. III. STATEMENT OF WORK: The contractor shall provide supervision, manpower, and materials to provide a replacement plan to replace ASTM A307 bolts currently installed in the facility to the required ASATM A193 bolts as the appropriate fastener for steam and hot water piping. Contractor shall locate and document all ASTM 307 bolts that are installed on high and medium pressure steam and hot water piping Areas to inspect include: 73 Air handling units, Penthouse 8th floor mechanical room, BF118 Mechanical Room, Emergency Room Mechanical Room, Research building Mechanical Room, Sub-basement Mechanical Room, 1st floor Mechanical Room, 2nd floor Mechanical Room, 3rd floor Mechanical Room, 5th floor Mechanical Room and Central Boiler Plant. Contractor to cut and remove insulation from flanges that are covering the bolts Contractor shall prioritize replacement plan from high and medium pressure steam and hot water piping systems operating over 50 pounds per square inch. Contractor shall provide report consisting of locations of ASTM 307 bolts with quantities at each equipment IMPORTANTR NOTE: This RFI (Request for Information) is for information only. No award will be made from this RFI. Please communicate via e-mail to frances.basham@va.gov by 15:00 on 10/24/2025 as to your company s ability to perform service per this brief Scope of Work. If interested, please provide the following: Please state your company s business size Please provide SAM UEI number If you have a FSS/GSA contract that includes this service Provide FSS/GSA contract number if applicable

From Sources Sought posted on Oct 17, 2025

Notice history

1
  1. Sources Sought LATEST Posted Oct 17, 2025

Details

Solicitation number 36C25926Q0034
Notice ID bb11692517d4478bb526158662e91625
Notice type Sources Sought
Product / Service (PSC) Z2DZ
NAICS 236220
Set-aside Veteran Set Aside
Place of performance Oklahoma City, Oklahoma
Archive date Dec 23, 2025

Award Information

Awardees
0

Documents

1
View on SAM.gov

Contacts

primary
Frankie Basham

Contracting Officer

Email

Phone

Agency

VETERANS AFFAIRS, DEPARTMENT OF
VETERANS AFFAIRS, DEPARTMENT OF
NETWORK CONTRACT OFFICE 19 (36C259)

Place of Performance

Department of Veterans Affairs Oklahoma City VA Medical Center
921 N.E. 13th St.
Oklahoma City, Oklahoma 73104
USA

Dates

Posted Oct 17, 2025 9 months ago
Last Updated Aug 06, 2026 2 days ago
Due Oct 24, 2025 9 months ago