Contacts, documents and full notice history are available with a subscription.
Solicitation Expired 4 notices 9 documents

Z1DA--ALBANY 8C,9D & 10C Door install/retrofit 2.0 36C24226Q0220

Solicitation 36C24226Q0220 Copied Notice ID 447aaffdecde4e1a95cd6612c486861f Copied VETERANS AFFAIRS, DEPARTMENT OF — 242-NETWORK CONTRACT OFFICE 02 (36C242)
SAM.gov
Posted
Dec 23, 2025
Deadline
Jan 02, 2026
Set-aside
None
NAICS
236220
PSC
Z1DA

Summary

AI-generated · Dec 17, 2025

Furnish and install entrance and security doors at Albany VAMC locations 8C, 9D, and 10C. For 8C, install a new gypsum wall board wall with swinging wood double doors that include vision lights and access control. For 9D, relocate the storefront door system from 10D and add the missing door to that system. For 10C, the existing storefront door with side light must be replaced with a door that swings in the opposite direction; a new door inset should be provided, and new window film must be included. Projected construction magnitude is between $25,000 and $100,000.

A formal solicitation for the same scope has been issued, with solicitation materials (information for bid details, specifications, drawings, and contract forms) available electronically on beta.SAM.gov. The awards section shows two awards listed, but no award amounts are provided yet.

Page 2 of 2 PRE-SOLICITATION NOTICE THIS PRE-SOLICITATION NOTICE IS TO INFORM YOU THAT THE STRATTON VA MEDICAL CENTER, LOCATED AT 113 HOLLAND AVE, ALBANY, NY 12208 WILL BE POSTING A SOLICITATION ON OR ABOUT DECEMBER 2, 2025, FOR THE ALBANY VAMC FURNISH & INSTALL ENTRANCE/SECURITY DOORS AT 8C, 9D & 10C PROJECT. The Stratton VA Medical Center (VAMC) located at 113 Holland Avenue, Albany, New York is requesting a contract to provide all labor and materials to furnish, install and rework Security/Entrance doors at the following location: 8C: New Gypsum Wall Board (GWB) wall with swinging wood double doors with vison lights & access control. 9D: Relocate storefront door system from 10D and add missing door to system. 10C: Existing storefront door with side light system, must have door with opposite swing. New door inset to be provided. New window film to be included. This procurement will be a 100% set-aside for Service Disabled Veteran Owned Small Businesses. The NAICS code is 236220. The small business standard is $45.0 Million. The magnitude of construction per FAR Part 36.204 is between $25,000 and $100,000. Solicitation materials consisting of the Information for Bid Details, Specifications, Drawings and Contract Forms will be available on beta.SAM.gov in electronic format only. The POC for this project will be Terry Fraser and can be reach at email at terry.fraser@va.gov.

From Presolicitation posted on Dec 16, 2025

FURNISH & INSTALL ENTRANCE/SECURITY DOORS at 10C, 9D & 8C ALBANY VAMC

From Solicitation posted on Dec 16, 2025

Stratton VA Medical Center Albany, New York Statement of Work (SOW) FURNISH & INSTALL ENTRANCE/ SECURITY DOORS at 10C & 9D General Scope of Work: Stratton Veterans Administration Medical Center, located at 113 Holland Avenue, Albany NY 12208 is requesting a contract to provide all labor and materials to furnish, install and rework Security/Entrance doors at the following location: 10C: Existing storefront door with side light system, must have door with opposite swing. New door inset to be provided. New window film to be included. 9D: Relocate storefront door system from 10D and add missing door to system. Work Required: 9D Relocate existing storefront sidelight system from 10C to 9D and add door to system. Contractor will provide all materials, labor and travel to relocate existing storefront door system from 10C to 9D. Contractor will provide all materials, labor and travel to return the 10D walls and flooring to original by matching existing finishes upon removal of storefront system. 10C Contractor will provide all materials, labor and travel to provide NEW storefront door (from Right Hand Reverse(RHR) to Left Hand Reverse (LHR). Contractor will provide all materials, labor and travel to install NEW hardware and door to LHR swing door. Existing door hardware includes: Four heavy duty ball bearing butt hinges. Push side Von Duprin 99 rim exit device with quiet latch retraction (QEL). Push side request to exit with jamb mounted strike. Push side Nabco GT 710 low energy operator bronze finish. Pull side bronze finish thought bolted wire pull handle with cylinder hole. Contractor will provide all materials, labor and travel required to adapt existing access control system to a LHR swing door system. Contractor will provide all materials, labor and travel required to install new window film as indicated in attached photos. Vendor will be required to confirm all measurements on-site. Provided by VA: 115VAC power above ceiling for operator & exit device power supply All required relocations of sprinkler heads VA Police Physical Security will provide port and address information for programming the system into the existing Lenel platform The following is required for this contract: All work will be in accordance with: NFPA 72: National Fire Alarm and Signaling Code. NFPA 70E: Standard for Electrical Safety in the Workplace. NFPA 70: National Electrical Code Articles 517, 645 & 800. NFPA 77: Recommended Practice on Static Electricity. NFPA 99: Healthcare Facilities. NFPA 101: Life Safety Code. Period of Performance One (1) Week after contract award- Submittals due. One (1) Week-Required submittal review. One (1) Week after all materials arrive- Work starts One (1) Week-To complete work. TOTAL Four (4) Weeks plus material lead time. Attachments: Door sample and placement. Door locations. Aluminum Door Spec. Glazing Spec. Location of Door on 9D Relocated from 10C 10C WINDOW FILM SAMPLE SECTION 08 44 13 GLAZED ALUMINUM CURTAIN WALLS GENERAL DESCRIPTION: This section specifies glazed aluminum curtain wall system. Thermally isolated, pressure equalized on interior. Type: Unit and Mullion system to include following: Uninsulated Metal Panels. Closures, trim, subsills and flashings. Column covers. Fasteners, anchors, and related reinforcement. RELATED WORK: Glazing: Section 08 80 00, GLAZING. QUALITY ASSURANCE: Qualifications: Approval by Contracting Officer Representative (COR) is required of products or services of proposed manufacturer, suppliers and installers, and will be based upon submission by Contractor of certification that: Manufacturers Qualifications: Manufacturer with five (5) years continuous documented experience in fabrication, of glazed aluminum curtain wall systems of similar types and for projects of equivalent size. Installer: Manufacturer approved in writing who has continuously installed glazed aluminum curtain walls systems of similar types and for projects of equivalent size for previous five (5) years. DELIVERY, STORAGE AND HANDLING: Refer to AAMA CW 10 for care and handling of architectural aluminum from shop to site. Prior to packaging for shipment from factory, mark wall components to correspond with shop and erection drawings and their placement location and erection sequence. Prior to shipment from factory, place knocked down lineal curtain wall members in cardboard containers and cover finished surfaces of members with protective covering of adhesive paper, waterproof tape, or strippable plastic. Do not cover metal surfaces that will be in contact with sealants after installation. PROJECT CONDITIONS: Field Measurements: Where glazed aluminum curtain wall systems are indicated to fit to other construction, verify dimensions of other construction by field measurements before fabrication and indicate measurements on shop drawings. Coordinate fabrication schedule with construction progress to avoid delaying Work. APPLICABLE PUBLICATIONS: Publications listed below form a part of this specification to extent referenced. Publications are referred to in text by basic designation only. American Architectural Manufacturers Association (AAMA): MCWM-1-89 Metal Curtain Wall Manual CW 10-12 Care and Handling of Architectural Aluminum from Shop to Site CW 13-85 Structural Sealant Glazing Systems (A Design Guide) 503-08 Field Testing of Metal Storefronts, Curtain walls and Sloped Glazing Systems American Society of Civil Engineers (ASCE): ASCE 7-10 Minimum Design Loads for Buildings and Other Structures ASTM International (ASTM): A36/A36M-12 Structural Steel A123/A123M-13 Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products A193/A193M-14a Alloy Steel and Stainless-Steel Bolting Materials for High Temperature Service A307-14 Carbon Steel Bolts and Studs, 60,000 PSI Tensile Strength B209-14 Aluminum and Aluminum Alloy Sheet and Plate B211-12 Aluminum and Aluminum Alloy Bar, Rod, Wire B221-14 Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes and Tubes B316/B316M-10 Aluminum and Aluminum Alloy Rivet and Cold-Heading, Wire, and Rods C578-14a Rigid Cellular Polystyrene Thermal Insulation C920-14a Elastomeric Joint Sealants C794-10 Standard Test Method for Adhesion-In-Peel of Elastomeric Joint Sealants. C1193-13 Guide for Use of Joint Sealants C1363-11 Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus C1521-13 Practice for Evaluating Adhesion of Installed Weatherproofing E84-14 Surface Burning Characteristics of Building Materials E413-10 Classification for Rating Sound Insulation American Welding Society, Inc. (AWS): D1.2/D.1.2M-06(R2014) Structural Welding Code Aluminum National Association of Architectural Metal Manufacturers (NAAMM): 500 Series (2006) Metal Finishes Manual Society for Protective Coatings (SSPC) Paint 25-97 (2004) Zinc Oxide, Alkyd, Linseed Oil Primer for Use Over Hand Cleaned Steel Type 1 and Type II Paint 20-82 (2019) Zinc-Rich Coating, Type I-Inorganic, and Type II-Organic. U.S. Veterans Administration: Physical Security Design Manual for VA Facilities (VAPSDG); Life Safety Protected Architectural Design Manual for VA Facilities (VASDM) Environmental Protection Agency (EPA): 40 CFR 59(2014) National Volatile Organic Compound Emission Standards for Consumer and Commercial Products WARRANTY: Construction Warranty: Comply with FAR clause 52.246-21, Warranty of Construction . PRODUCTS SYSTEM DESCRIPTION: Design Requirements: Shop unitized assembly. Maximum wall framing member deflection, in a direction normal to plane of wall: 1/175 of its clear span or 20 mm (3/4 inch), whichever is less, when designed in accordance with requirements of AAMA TIR A11 and tested in accordance with ASTM E330/E330M. Maximum wall framing member deflection when a gypsum wallboard surface is affected: 1/360 of span. Maximum Framing Member Permanent Deformation: 0.2 percent of its clear span when tested in accordance with ASTM E330/E330M for a minimum test period of 10 seconds at 1.5 times design wind pressures indicated as part of structural drawing wind load requirements. No glass breakage, or damage to fasteners, hardware or accessories is permitted due to deformation design requirements indicated. Provide system complete with framing, mullions, trim, fasteners, anchors, accessories, concealed auxiliary members, and attachment devices for securing wall to structure as specified or indicated. Unless noted otherwise, comply with AAMA MCWM 1. Obtain all components from single manufacturer. Fully coordinate system accessories directly incorporated and adjacent to contiguous related work and ensure materials compatibility, deflection limitations, thermal movements, and clearances and tolerances as indicated or specified. Coordinate continuity with adjacent thermal, weather, air and vapor barriers. Provide system with adequate allowances for expansion and contraction of components and fastenings to prevent buckling damage, joint seal failure, glass breakage, undue stress on fastening or other detrimental effects. For design purposes, base provisions for thermal movement on assumed ambient temperature range of from 18 degrees C to 49 degrees C (0 degrees F to 120 degrees F). Provide wall system to accommodate tolerances in building frame and other contiguous work as indicated or specified. MATERIALS: Extruded Aluminum Framing Members: ASTM B221M (B221); 6063-T5 extruded aluminum for non-structural components or 6063-T6 extruded aluminum for structural members; temper and alloy as recommended by manufacturer. Sheet Aluminum: ASTM B209M (B209); 6065-T5 temper and alloy as recommended by manufacturer. Formed flashing and closures: Minimum 1.58 mm (0.062 inch) thick aluminum, in finish as selected. Extruded sill members: Minimum 1.58 mm (0.062 inch) thick aluminum, in finish as selected. Fasteners: For Framework Connections: ASTM B211M (B211) 2024 T4 aluminum, ASTM A193/A193M B8 300 series, stainless steel, and ASTM B316 aluminum rivets, as required by connection. For Anchoring Glazed Aluminum Curtain Wall to Support Structure: ASTM A307 zinc plated steel fasteners. Shims: Metal or plastic. Glazing Materials: As specified under Section 08 80 00, GLAZING. Glazing Gaskets: Interior: Continuous, closed cell PVC foam sealant tape, sealed at corners. Glass Sizes and Clearances: Accommodate up to 1/4-inch glazing. Sizes indicated are nominal. Verify actual sizes required by measuring frames. Coordinate dimensions for glass and glass holding members to meet applicable minimum clearances as recommended by glass manufacturers. Do not nip glass to remove flares or to reduce oversized dimensions. All cutting is to occur in factory. Glass Setting Materials: Provide head bead and drive wedge required for glass installation to suit curtain wall system in accordance with manufacture s recommendations. FABRICATION: Curtain wall components are to be of materials and thickness indicated in construction documents. Details indicated are representative of required design and profiles. Maintain sightlines. Unless specifically indicated or specified otherwise, methods of fabrication and assembly are to be at discretion of curtain wall manufacturers. Perform fitting and assembling of components in shop to maximum extent practicable. Anchorage devices are to permit adjustment in three directions. No exposed fasteners are permitted. Joints: Joints exceeding +1.5 mm (+1/16") are to be mechanically fastened. Protection and Treatment of Metals: Remove from metal surfaces lubricants used in fabrication and clean off other extraneous material before leaving shop. Provide protection against galvanic action wherever dissimilar metals are in contact, except in case of aluminum in permanent contact with galvanized steel, zinc, stainless steel, or relatively small areas of white bronze. Paint contact surfaces with one coat bituminous paint conforming to MIL C 18480 or apply appropriate caulking material or nonabsorptive, noncorrosive, and non-staining tape or gasket between contact surfaces. Metal sills and Closures: Fabricate accessories, spandrel panels, trim closures of sizes and shapes indicated from similar materials and finish as specified for wall system. METAL FINISHES: In accordance with NAAMM AMP500 series. Anodized Aluminum: AA C22A44 Chemically etched medium matte with electrolytically deposited metallic compound, integrally colored coating Class 1 Architectural, 0.7 mil thick finish. Dyes will not be accepted. Dark bronze. EXECUTION PREPARATION: Take field dimensions and examine condition of substrates, supports, and other conditions under which work of this section is to be performed to verify that work may properly commence. Do not proceed with installation until unsatisfactory conditions have been corrected. Contact between aluminum and dissimilar metals are to receive a protective coating of bituminous paint for prevention of electrolytic action and corrosion. INSTALLATION: Install and erect glazed curtain wall system and all components in accordance with written directions of curtain wall manufacturer. Match profiles, sizes, and spacing indicated on approved shop drawings. Install glazed aluminum curtain wall system so as to maintain a virtually flat face cap, with no visible bowing. Install entire system so that fasteners are not visible. Tolerances: Maximum variation from plane or location shown on approved shop drawings: 3 mm per 3657 mm (1/8 inch per 12 feet) of length up to not more than 13 mm (1/2 inch) in any total length. Maximum offset from true alignment between two (2) identical members abutting end to end in line: 0.8 mm (1/32 inch). Sealant Space Between Curtain Wall Mullion and Adjacent Construction: Maximum of 19 mm (3/4 inch) and minimum of 6 mm (1/4 inch). ADJUSTING: Adjust doors to provide a tight fit at contact points and operate easily. Adjust weather-stripping to make even contact with surfaces. Adjust operating hardware and moving parts. CLEANING: Install curtain wall frame and associated metal to avoid soiling or smudging finish. Clean metal surfaces promptly after installation, exercising care to avoid damage to coatings. Remove excess glazing and sealant compounds, dirt, and other substances. Follow recommendations of manufacturer in selection of cleaning agents. Do not use cleaning agents containing ammonia or other compounds that might damage finished metal surfaces. Replace cracked, broken, and defective glass with new glass at no additional cost to Government. Just prior to final acceptance of curtain wall system clean glass surfaces on both sides, remove labels, paint spots, compounds, and other defacements, and clean metal fixed panels. Remove and replace components that cannot be cleaned successfully. DEMONSTRATION, TESTING, AND ACCEPTANCE: Instruct Government s personnel in proper operation and maintenance of door equipment. Train personnel in procedures to follow in event of operational failures or malfunctions. Acceptance: At completion of project, and as a condition of acceptance, door and systems are to be operated for a period of fifteen (15) consecutive calendar days without breakdown. PROTECTION: After installation, protect windows, and other exposed surfaces from disfiguration, contamination, contact with harmful materials, and from other construction hazards that will interfere with their operation, or damage their appearance or finish. Protection methods are to be in accordance with recommendations of product manufacturers or of respective trade association. Remove paper or tape factory applied protection immediately after installation. Clean surfaces of mortar, plaster, paint, smears of sealants, and other foreign matter to present neat appearance and prevent fouling of operation. In addition, wash with a stiff fiber brush, soap and water, and thoroughly rinse. Where surfaces become stained or discolored, clean or restore finish in accordance with recommendations of product manufacturer or respective trade association. END - SECTION 08 80 00 GLAZING GENERAL DESCRIPTION This section specifies the following: Glass. Glazing materials and accessories for both factory and field glazed assemblies. RELATED WORK Section 08 44 13, GLAZED ALUMINUM CURTAIN WALLS Glazed Curtain Walls: Glazed Curtain Walls. LABELS Permanent labels: Locate in corner for each pane. Label in accordance with ANSI Z97.1 and SGCC label requirements. Tempered glass. PERFORMANCE REQUIREMENTS General: Design glazing system consistent with guidance and practices presented in the GANA Glazing Manual, GANA Laminated Glazing Manual, and GANA Sealant Manual, as applicable to project. Installed glazing is to withstand applied loads, thermal stresses, thermal movements, building movements, permitted tolerances, and combinations of these conditions without failure, including loss or glass breakage attributable to defective manufacture, fabrication, or installation; failure of sealants or gaskets to remain watertight and airtight; deterioration of glazing materials; unsafe engagement of the framing system; deflections beyond specified limits; or other defects in construction. Glazing Unit Design: Design glass, including engineering analysis meeting requirements of authorities having jurisdiction. Thicknesses listed are minimum. Coordinate thicknesses with framing system manufacturers. Design glass in accordance with ASTM E1300, and for conditions beyond the scope of ASTM E1300, by a properly substantiated structural analysis. Maximum Lateral Deflection: For glass supported on all four edges, limit center-of-glass deflection at design wind pressure to not more than the structural capacity of the glazing unit, the threshold at which frame engagement is no longer safely assured, 1/100 times the short-side length, or 19 mm (0.75 inch), whichever is less. DELIVERY, STORAGE AND HANDLING Delivery: Schedule delivery to coincide with glazing schedules so minimum handling of crates is required. Do not open crates except as required for inspection for shipping damage. Storage: Store cases according to printed instructions on case, in areas least subject to traffic or falling objects. Keep storage area clean and dry. Handling: Unpack cases following printed instructions on case. Stack individual windows on edge leaned slightly against upright supports with separators between each. Protect laminated security glazing units against face and edge damage during entire sequence of fabrication, handling, and delivery to installation location. Provide protective covering on exposed faces of glazing plastics, and mark inside as "INTERIOR FACE" or "PROTECTED FACE": Treat security glazing as fragile merchandise and packaged and shipped in export wood cases with width end in upright position and blocked together in a mass. Storage and handling to comply with manufacturer's directions and as required to prevent edge damage or other damage to glazing resulting from effects of moisture, condensation, temperature changes, direct exposure to sun, other environmental conditions, and contact with chemical solvents. Protect sealed-air-space insulating glazing units from exposure to abnormal pressure changes, as could result from substantial changes in altitude during delivery by air freight. Provide temporary breather tubes which do not nullify applicable warranties on hermetic seals. Temporary protections: The glass front and polycarbonate back of glazing are to be temporarily protected with compatible, peelable, heat-resistant film which will be peeled for inspections and re applied and finally removed after doors and windows are installed at destination. Since many adhesives will attack polycarbonate, the film used on exposed polycarbonate surfaces is to be approved and applied by manufacturer. Edge protection: To cushion and protect glass clad, and polycarbonate edges from contamination or foreign matter, the four (4) edges are to be sealed the depth of glazing with continuous standard thickness thermoplastic rubber tape. Alternatively, continuous channel shaped extrusion of thermoplastic rubber are to be used, with flanges extending into face sides of glazing. PROJECT CONDITIONS: Field Measurements: Field measure openings before ordering tempered glass products to assure for proper fit of field measured products. APPLICABLE PUBLICATIONS: Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only. American Architectural Manufacturers Association (AAMA): 800 Test Methods for Sealants 810.1-77 Expanded Cellular Glazing Tape American National Standards Institute (ANSI): Z97.1-14 Safety Glazing Material Used in Building Safety Performance Specifications and Methods of Test ASTM International (ASTM): C542-05(2017) Lock-Strip Gaskets C716-06(2020) Installing Lock-Strip Gaskets and Infill Glazing Materials C794-18 Adhesion-in-Peel of Elastomeric Joint Sealants C864-05(2019) Dense Elastomeric Compression Seal Gaskets, Setting Blocks, and Spacers C920-18 Elastomeric Joint Sealants C964-20 Standard Guide for Lock-Strip Gasket Glazing D635-18 Rate of Burning and/or Extent and Time of Burning of Self-Supporting Plastic in a Horizontal Position E84-20 Surface Burning Characteristics of Building Materials E119-20 Standard Test Methods for Fire Test of Building Construction and Material E1300-16 Load Resistance of Glass in Buildings F1233-08(2019) Standard Test Method for Security Glazing Materials and Systems F1642/F1642M-17 Test Method for Glazing and Glazing Systems Subject to Airblast Loadings Code of Federal Regulations (CFR): 16 CFR 1201-10 Safety Standard for Architectural Glazing Materials Glass Association of North America (GANA): 2010 Edition GANA Glazing Manual 2008 Edition GANA Sealant Manual 2010 Edition GANA Protective Glazing Reference Manual International Code Council (ICC): IBC International Building Code Intertek Testing Services Warnock Hersey (ITS-WHI) National Fire Protection Association (NFPA): 80-16 Fire Doors and Windows 252-12 Fire Tests of Door Assemblies National Fenestration Rating Council (NFRC) Safety Glazing Certification Council (SGCC) 2012: Certified Products Directory (Issued Semi-Annually). Underwriters Laboratories, Inc. (UL): 9-08(R2009) Fire Tests of Window Assemblies 263-14 Fire Tests of Building Construction and Materials Department of Veterans Affairs: Architectural Design Manual for VA Facilities (VASDM) PRODUCT GLASS Provide minimum thickness stated and as additionally required to meet performance requirements. Provide minimum 6 mm (1/4 inch) thick glass units unless otherwise indicated. Obtain glass units from single source from single manufacturer for each glass type. Clear Glass: ASTM C1036, Type I, Class 1. GLAZING ACCESSORIES As required to supplement the accessories provided with the items to be glazed and to provide a complete installation. Ferrous metal accessories exposed in the finished work are to have a finish that will not corrode or stain while in service. Fire rated glazing to be installed with glazing accessories in accordance with the manufacturer s installation instructions. Spacers: ASTM C864: Channel shape having a 6 mm (1/4 inch) internal depth. Flanges not less 2.4 mm (3/32 inch) thick and web 3 mm (1/8 inch) thick. Lengths: 25 to 76 mm (1 to 3 inches). Shore A hardness of 40 to 50 Durometer. Glazing Tapes: Semi solid polymeric based closed cell material exhibiting pressure sensitive adhesion and withstanding exposure to sunlight, moisture, heat, cold, and aging. Shape, size and degree of softness and strength suitable for use in glazing application to prevent water infiltration. Complying with AAMA 800 for the following types: AAMA 810.1, Type 1, for glazing applications in which tape acts as the primary sealant. AAMA 810.1, Type 2, for glazing applications in which tape is used in combination with a full bead of liquid sealant. Spring Steel Spacer: Galvanized steel wire or strip designed to position glazing in channel or rabbeted sash with stops. Glazing Clips: Galvanized steel spring wire designed to hold glass in position in rabbeted sash without stops. Glazing Points (Sprigs): Pure zinc stock, thin, flat, triangular or diamond shaped pieces, 6 mm (1/4 inch) minimum size. Glazing Gaskets: ASTM C864: Firm dense wedge shape for locking in sash. Soft, closed cell with locking key for sash key. Flanges may terminate above the glazing beads or terminate flush with top of beads. EXECUTION EXAMINATION Verification of Conditions: Examine openings for glass and glazing units; determine they are proper size; plumb; square; and level before installation is started. Verify that glazing openings conform with details, dimensions and tolerances indicated on manufacturer is approved shop drawings. Review for conditions which may adversely affect glass and glazing unit installation, prior to commencement of installation. Do not proceed with installation until unsatisfactory conditions have been corrected. Verify that wash down of adjacent masonry is completed prior to erection of glass and glazing units. PREPARATION For sealant glazing, prepare glazing surfaces in accordance with GANA Sealant Manual. Determine glazing unit size and edge clearances by measuring the actual unit to receive the glazing. Shop fabricate and cut glass with smooth, straight edges of full size required by openings to provide GANA recommended edge clearances. Verify that components used are compatible. Clean and dry glazing surfaces. Prime surfaces scheduled to receive sealants, as determined by preconstruction sealant-substrate testing. INSTALLATION GENERAL Install in accordance with GANA Glazing Manual, GANA Sealant Manual, IGMA TB-3001, and IGMA TM-3000 unless specified otherwise. Glaze in accordance with recommendations of glazing and framing manufacturers, and as required to meet the Performance Test Requirements specified in other applicable sections of specifications. Set glazing without bending, twisting, or forcing of units. Do not allow glass to rest on or contact any framing member. Glaze doors and operable sash, in a securely fixed or closed and locked position, until sealant, glazing compound, or putty has thoroughly set. Tempered Glass: Install with roller distortions in horizontal position unless otherwise directed. INSTALLATION INTERIOR WET/DRY METHOD (TAPE AND SEALANT) Cut glazing tape to length and install against permanent stops, projecting 1.6 mm (1/16 inch) above sight line. Place setting blocks at 1/4 points with edge block no more than 150 mm (6 inches) from corners. Rest glazing on setting blocks and push against tape to ensure full contact at perimeter of pane or unit. Install removable stops, spacer shims inserted between glazing and applied stops at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line. Fill gaps between pane and applied stop with sealant to depth equal to bite on glazing, to uniform and level line. Sealant type is to be compatible with glazing tape. Trim protruding tape edge. REPLACEMENT AND CLEANING Clean new glass surfaces removing temporary labels, paint spots, and defacement after approval by COR. Replace cracked, broken, and imperfect glass, or glass which has been installed improperly. Leave glass, putty, and other setting material in clean, whole, and acceptable condition. PROTECTION Protect finished surfaces from damage during erection, and after completion of work. Strippable plastic coatings on colored anodized finish are not acceptable. Autodesk Build Construction Management Platform Autodesk build construction management platform: The Contractor shall utilize VISN 2 Autodesk Build Construction management platform, also called Autodesk Construction Cloud (ACC). Access to the platform and training portal will be provided by VISN 2 through project Contracting Officer Representative (COR) at no cost for the duration of the project. Autodesk Build is the management and collaborative environment that VISN 2 uses for all its Non-Recurring Maintenance (NRM), Minor Program projects, Feasibility Studies, Commissioning and Retro-Commissioning contracts. There is no user, license, or subscription fee to the contractor for using this cloud-based platform. The Contractor shall accomplish and complete the following tasks upon award of contract: Request access to ACC platform and ProductivityNOW eLearning Site to project VA COR within 14 days of contract award. Only staff that shall utilize the platform to be granted access. Examples: Project manager, sub-contractors POC, Site manager, Safety officer, etc. The access request shall be in writing and include a list of staff. The list shall include the following information: Full Name Company Name Email Address Role/Position on the project (i.e., Project manager, site super) Contractor staff granted access to the ACC platform shall complete ACC training through ProductivityNOW eLearning platform and provide certificates of completion to COR within 12 Calendar days of access being granted. Initial access to ProductivityNOW eLearning platform shall expire after 12 Calendar days after online access is granted. D) Additional Staff and Subcontractors can be added at any time with a request submission to the project COR. The contractor shall only use the ACC platform for contract required submissions, official project correspondence to be acknowledged, reviewed, and actioned by the responsible party. No additional time shall be added to the contract, nor an increase in contract amount provided for the contractor s failure to utilize the ACC platform as the project s official communication and collaboration system. Any correspondence out of platform shall not be the governing authority contradicting direction and will be at the contractor s expense. Official project correspondence and collaboration include but not limited to: RFIs, submittals, schedules, shutdown requests, actionable tasks, reports, testing, safety inspections, photos, and site surveys. Contractor shall inform the COR of any staff changes within 2 business days from the change. Staff changes pertain to staff granted access to the ACC platform. Contractor shall request termination of access, replacement of personnel and/or any other action that might impact the contractor s ability to maintain required utilization of the platform. Contractor submission requirements cannot be accepted for work to begin without meeting all ACC Platform requirements outlined herein, including completing required ACC platform training.

From Solicitation posted on Dec 22, 2025

INSTRUCTIONS, CONDITIONS AND OTHER STATEMENTS TO BIDDERS/OFFERORS GENERAL INTENTION REQUESTS FOR INFORMATION (RFI): To obtain clarifications and/or additional information concerning the contract requirements or specifications, submit a written RFI via email to terry.fraser@va.gov. RFIs will be responded to as necessary in amendment format which will be posted on http://www.beta.sam.gov The deadline for submission of RFIs for this solicitation is Monday, December 29, 2025, at 3:00 PM (EST). No questions will be answered after this date/time unless determined to be in the best interest of the Government as determined by the Contracting Officer. Telephone RFIs will not be accepted or returned. BASIS FOR AWARD Contract award will be made to the responsive, responsible bidder submitting the lowest price in accordance with FAR Part 14 Sealed Bidding. RESPONSIBILITY REQUIREMENTS A Determination of Responsibility shall be accomplished for the apparent awardee prior to processing the award. The above information, along with other information obtained from Government systems, such as the OSHA and EPA online inspection history databases will be used to make the Determination of Responsibility. Failure to affirm being within the guidelines above or submit this information may result in a determination of Non-Responsibility for the bidder/offeror. NOTE: Any information received by the Government that would cause for a negative Determination of Responsibility may make the bidder/offeror ineligible for award. This requirement is applicable to all subcontracting tiers, and prospective prime contractors are responsible for determining the responsibility of their prospective subcontractors. DELIVERY OF BIDS There will not be a face-to-face public bid opening. In accordance with FAR 14.202-8, send all submission documents via email to terry.fraser@va.gov by 1:00 PM EST Friday, January 2, 2026. Bids received after this time may be rejected. All Contractors providing an electronic bid submission must still meet all requirements listed under Bid Submission in the solicitation. The bid opening and public reading of the bids will be via teleconference. Bidders may call +1 347-566-4838,, at 1:15 PM EST and enter participant code 279 385 442# to join. The bid submission emails will be kept in an electronic folder unread until 1:15 PM EST when they will be opened and read to the public. Files should be in Adobe* PDF (Portable Document Format) Files: Size: Maximum size of the e-mail message shall not exceed five (5) megabytes. If the size limits are exceeded, the VA may not receive the file and/or you may not be considered. Only one email is permitted. This email should contain at least the following as separate attachments: One (1) signed SF1442 with amendments acknowledged. Include response to FAR 52.204-8(2) (i) or (ii) Annual Representations and Certifications Response to FAR 52.209-13(b)(1) or (2) Violation of Arms Controls Treaties or Agreements One (1) complete signed SF 24 Bid Bond and Power of Attorney. One (1) safety or environmental violations and experience modification rate. One (1) Class Deviation to Implement SDVOSB and VOSB Certification Requirements

From Solicitation posted on Dec 23, 2025

Notice history

4
  1. Presolicitation Posted Dec 16, 2025 View
  2. Solicitation Posted Dec 16, 2025
    • Description: Description was updated
    • Notice Type: PresolicitationSolicitation
    • Response Deadline: Dec 15, 2025Dec 31, 2025
    • Set-Aside: NoneNone
  3. Solicitation Posted Dec 22, 2025
    • Description: Description was updated
    • Response Deadline: Dec 31, 2025Dec 26, 2025
  4. Solicitation LATEST Posted Dec 23, 2025
    • Description: Description was updated
    • Response Deadline: Dec 26, 2025Jan 02, 2026

Details

Solicitation number 36C24226Q0220
Notice ID 447aaffdecde4e1a95cd6612c486861f
Notice type Solicitation
Product / Service (PSC) Z1DA
NAICS 236220
Archive date Feb 01, 2026

Award Information

Awardees
0

Contacts

primary
Terry Fraser

Contract Specialist

Email

Agency

VETERANS AFFAIRS, DEPARTMENT OF
VETERANS AFFAIRS, DEPARTMENT OF
242-NETWORK CONTRACT OFFICE 02 (36C242)

Place of Performance

Dates

Posted Dec 23, 2025 7 months ago
Last Updated Aug 06, 2026 2 days ago
Due Jan 02, 2026 7 months ago