USCGC Mobile Bay 70Z08526Q0003061
Summary
AI-generated · Jan 31, 2026Perform maintenance and inspection of the Hi-Fog Water Mist Fire Suppression System on the USCGC Mobile Bay, stationed in Sturgeon Bay, WI. The contractor must be certified and capable of maintaining the system, set it up for testing, conduct the water mist system test, and return the system to normal operation, ensuring all connections, fittings, and equipment function correctly. This includes the 5-year system inspection and the required annual checks, using MPC guidance R-A-13380, R-C-14526, and R-M-13373.
Replacement parts to be included in the inspection: 2 water filters (R1/2, 60-micron, E31048); 1 low-pressure freshwater safety valve (M-0010165); 2 SVM20 DNV valve rebuild kits (V14020); 2 check valve sets—low-pressure water inlet (V93000); 2 check valve sets—high-pressure water outlet (V93002); 28 gas release valve seal kits (G40226.A). Renewal/exchange: 29 nitrogen cylinders with certification. Any discrepancies found must be noted and corrected only if there is no additional cost; if correction would incur costs beyond the quote, route the discrepancy to the customer before proceeding. Period of performance is a multi-day window in March 2026 at USCGC Mobile Bay.
STATEMENT OF WORK CGC MOBILE BAY OPFAC: 09-17503 LOCATION: Sturgeon Bay, WI EQUIPMENT: Hi-Fog Water Mist Fire Suppression System COMPONENT AFFECTED: 5-YEAR AND ANNUAL INSPECTION OF SYSTEM Contractor must be certified & capable of performing maintenance on a HI-FOG Water Mist System. Contractor must set up water mist system for testing; complete the water mist system test; and place water mist system back in normal operation once test is completed. Contractors must ensure all connections, fittings, and equipment within the water mist system are operating correctly as well. Contractor must also complete the 5 Year System Inspection. Contractors shall use MPC s R-A-13380, R-C-14526, R-M-13373 as guidance. Replacement Parts to be included in 5-Year Annual Inspection: 2 - FILTER WATER FILTER R1 1/2, 60-MICROMETER (E31048) 1 - LOWPRESSURE FRESH WATER SAFETY VALVES (M-0010165) 2 - SVM20 DNV VALVE REBUILD KITS (V14020), 2 - CHECK VALVE SET - LOWPRESSURE WATER INLET - (V93000), 2- CHECK VALVE SET - HIGH PRESSURE WATER OUTLET - (V93002), 28 - GAS RELEASE VALVESEAL KIT (G40226.A) Renewal/Exchange: 29 - N2 Cylinders with certification Any discrepancies found shall be noted; and corrected only if no other cost is needed. If any discrepancy causes cost outside the quote, this shall be routed through customer before discrepancy is corrected. Period of Performance: 09 - 13 March, 2026 Unit/Location: USCGC MOBILE BAY 36 South Neenah Ave Sturgeon Bay, WI 54235 POC: CWO Joshua Deisher (574) 601-9308 joshua.l.deisher@uscg.mil
From Combined Synopsis/Solicitation posted on Jan 30, 2026Notice history
1-
Combined Synopsis/Solicitation LATEST Posted Jan 30, 2026
Details
Award Information
Not yet awarded
Contacts
Phone
Phone
Agency
Place of Performance
USA