TSS Ductless System Installation at EWR ATCT (Newark, N.J.) TSS_Ductless_System_Installation_EWR_ATCT
Summary
AI-generated · Nov 18, 2025Mechanical installation of three indoor wall-mounted units and one six-ton heat pump at EWR ATCT. Mount and anchor the units to an exterior concrete wall using an L-bracket steel frame; coordinate concrete-core penetrations for piping, electrical, and drainage, and install wall waterproofing. Insulate all refrigerant and condensate piping above the ceiling, test and charge the system to verify operation, and install a dedicated 208V 3-phase power circuit with a NEMA 4X, 60A stainless steel disconnect at the outdoor unit. Provide power and control conduit/wiring to/from all units, complete penetrations through the concrete wall and roof deck, and patch/flash the roof as required to maintain the existing roof warranty.
Controls integration and commissioning: tie the mini-split system into the FAA Schneider Electric EcoStruxure DDC system via BACnet, and install one IP-IO module at VAV-17 for coordinated backup cooling enable/disable. Submit point list, graphics, and a control narrative to the COR for approval; program unit set points and update AHU-3 supply air setpoints; support system commissioning to validate operation. Structural/interior work includes concrete core penetrations for pipes/conduits, providing and securing framing for all units and steel plates as shown in drawings, supporting pipes and conduits, and completing wall restoration and painting.
Mechanical Install (3) indoor wall-mounted units, along with all refrigerant and drain piping. Install (1) 6-ton heat pump. Unit to be anchored to exterior concrete wall via on L-bracket steel frame. Coordinate core penetrations through concrete wall for piping, electrical, and drain lines. Installation to include all wall waterproofing. Provide and insulate all refrigerants and condensate piping above ceiling Test and charge system to verify operation. Electrical Install new dedicated 208V, 3-phase power circuit Provide NEMA 4X, 60A non-fused stainless steel disconnect at outdoor unit Provide power and control conduit and wiring to/from all units Penetrate concrete wall. Provide penetration and conduit through roof deck. Patch and flash roof as required to maintain new roof warranty through Carlisle Roof installer. Controls Integrate mini-split system into the existing FAA Schneider Electric EcoStruxure DDC system via BACnet Provide and install one IP-IO module at VAV-17 for coordinated backup cooling enable/disable Submit point list, graphics, and control narrative to COR for approval. Program unit set points, and update AHU-3 supply air setpoints Support commissioning of system to validate operation. Structural & Interior Concrete core penetration for pipes and conduits Provide support framing for all units and steel plates as shown in drawing. Provide support for pipes and conduits. Work to include wall restoration and painting.
From Sources Sought posted on Nov 17, 2025Notice history
1Details
Award Information
Not yet awarded
Contacts
Phone
Agency
Place of Performance
USA