Full and Open Competition Request for Pad-Mounted Transformer, Vance AFB WT18526408
Summary
AI-generated · Jun 02, 2026Provide a firm-fixed-price supply of a pad-mounted transformer for Vance AFB that meets the following HV/LV specs: Primary 12,470Y / 75 kV BIL with taps at 13094, 12783, 12470, 12159, 11847; six HV 200A wells and inserts, dead-front, loop feed; Secondary 240/120 Delta with 30 kV BIL; four LV bushings (6-hole spades); fluid/coolant Envirotemp FR3 or equivalent natural ester. Includes temperature rise of 65C, ONAN cooling, bayonets with Iso-Links fusing, a 2-position load-break switch, no arresters, and standard pad-mount cabinet plus required accessories (separate H0 HV bushing, liquid level gauge, pressure/vacuum gauge, dial-type thermometer, Schrader valve, drain and sample valve, pressure relief valve, and pad-mount green paint). Submittal requirements require manufacturer product data and transformer submittals for approval prior to award; compliance with Buy American Act is mandatory and the transformer must exclude prohibited materials. Delivery must occur within 140 days to Enid, OK, with all deliverables and certifications included in the submission.
Proposals will be evaluated on Low Price Technically Acceptable; offerors must be active in the System for Award Management at the time of submission, and quotes must remain valid for 90 days after the solicitation close. The government notes that funding may be unavailable and the procurement may be canceled; amendments may be issued and failure to acknowledge amendments could render a quote non-responsive. Attachments include photos of the damaged transformer.
This is a combined synopsis/solicitation for commercial items prepared in accordance with the format in FAR Subpart 12.6 and FAR 13. This announcement constitutes the only solicitation; quotes are being requested and a separate written solicitation will not be issued. Funds are not presently available for this requirement. No award will be made until funds are available. AFGSC and/or the Government reserves the right to cancel this solicitation, either before or after the closing date for receipt of proposals. In the event AFGSC or the Government cancels this solicitation, neither AFGSC nor the Government has any obligation to reimburse any offeror for any costs. It is the sole responsibility of all offerors to frequently check this posting on SAM.gov for any amendments, updated attachments, or changes to this solicitation. Failure to acknowledge and comply with posted amendments may result in a quote being deemed non-responsive. ASRC Federal Gulf State Constructors, LLC (AFGSC) Prime Contractor for the Government, intends to award a Firm-Fixed-Price for the purchase of a Pad-mounted Transformer. AFGSC is requesting quotes for the following, transformer must meet or exceed the specifications below: High Voltage (HV) Requirements Primary: 12470 GY / 7200 BIL: 75kV Taps: 13094, 12783, 12470, 12159, 11847 HV Bushings: (6) 200A Wells & Inserts, dead-front, loop feed Low Voltage (LV) Requirements Secondary: 240/120 Delta BIL: 30kV LV Bushings: (4) 6-hole spades Fluid / Coolant: Envirotemp FR3 or equivalent natural ester, biodegradable, non-toxic coolant Electrical / Mechanical Requirements: Temperature rise: 65C Cooling class: ONAN Fusing: Bayonets with Iso-Links Switch: 2-position Load Break Switch (LBOR) Arresters: None Cabinet depth: Standard Required Features/Accessories: Separate H0 bushing in HV cabinet Liquid level gauge Pressure/vacuum gauge Dial-type thermometer Schrader valve Drain & sample valve Pressure relief valve Pad-mount green paint Submittals: The supplier must submit manufacturer product data and transformer submittals for approval prior to an award. Buy American Act: All materials must comply with the Buy American Act. Prohibited Materials: The transformer must not contain mercury, toluene, chlorinated solvents, hydrolysable chlorine derivatives, ethylene-based glycol ethers, lead, hexavalent chromium, or Class 1 ozone-depleting chemicals. Period of Performance/Lead Time: Delivery must occur within 140 days. Delivery Address: AFGSC 140 Channel Street, Bld 288 Enid, OK 73705 Quote Validity: Quotes must remain valid for 90 days after the solicitation close date of July 1, 2026. This extended timeframe will provide the Government with the strongest opportunity to secure the necessary funding and ensure continuity in the procurement process. Instructions to Offerors: Quotes must be emailed to Betty Kliewer; betty.kliewer.ctr@us.af.mil NLT July 1, 2026 at 2:00 PM CST. No late entries will be considered or accepted. The quotes will be evaluated based on Low Price Technically Acceptable (LPTA). All interested vendors must be registered and active in the System for Award management (SAM) at the time of quote submission. Quotes submitted by vendors who are not active in SAM cannot be considered for award. Attachments: Pictures of the damaged transformer General Terms and Conditions Representations and Certifications Vendor Form (business information)
From Combined Synopsis/Solicitation posted on Jun 01, 2026Notice history
2-
-
Award Notice LATEST Posted Jul 23, 2026
Details
Award Information
Awardees
| Company Name | UEI | CAGE Code | Location |
|---|---|---|---|
| RESA SERVICE, LLC | K5W3LXQ31Y65 | 9LGT2 | Houston, TX |
Contacts
Phone
Agency
Place of Performance
USA