FEMA Thomasville Federal Regional Center Uninterruptable Power Supply Inspections 70FBR425Q00000153

Solicitation 70FBR425Q00000153 Copied Notice ID ba356760c2b1436a9131b02cee8ed06b Copied HOMELAND SECURITY, DEPARTMENT OF — REGION 4: EMERGENCY PREPAREDNESS AN
SAM.gov
Posted
Jul 08, 2025
Deadline
Jul 11, 2025
Set-aside
NONE
NAICS
541350
PSC
H349

Summary

AI-generated · Aug 24, 2025

Annual UPS inspections at FEMA Thomasville FRC consist of one Major PM and one Minor PM to ensure clean power to critical server-room loads. Major PM tasks include a thermal scan of all power connections, tightening loose connections, verifying converter and inverter transfer operation, exercising external maintenance bypass breakers, testing AC input failure with battery operation (customer approval), and confirming maintenance bypass switch operability. Battery-system checks involve measuring inter-cell and main-terminal ohmic values, cleaning or retorquing connections that fall below manufacturer values or drop more than 20% from baseline, and, if requested, opening the DC breaker or turning off the UPS charger. Minor checks (semi-annual) cover environmental conditions, ventilation clearances, proper installation and location, thorough visual inspection of structure, paint, frame, covers, accessories, fasteners, wiring condition, edge guards, and PCB connections, plus post-operation cleanup, a final report to the customer, and scheduling the next PM or repair work. Parts are not included; labor and mobilization are; work must meet IEEE standards and battery maker recommendations; all personnel must pass a background check. Location: FEMA Thomasville FRC, Thomasville, GA.

New notices add explicit unit specifications for the Thomasville UPS: ABB, Series SG, 80 kVA, VRLA batteries (40 batteries in one cabinet Sprinter Next), 87 Ah capacity, 365-minute runtime, model number S12v325fl. This clarifies the exact equipment to be inspected but does not change the overall scope of inspections or the firm-fixed-price arrangement; replacement parts and labor, if needed, are billed as time-and-material plus 15%.

The Purpose of this Firm Fixed Price (FFP) Solicitation is to procure Annual Uninterruptable Power Supply (UPS) Inspections, (1) Major PM inspection and (1) Minor PM inspection to ensure that the equipment is in good working condition to maintain clean power to critical loads in the server room at the FEMA Federal Regional Center (FRC) Thomasville, GA Facility. SCOPE OF WORK Annual and Semi-Annual UPS Inspections at FEMA Thomasville FRC Annual System Checks (Major) Thermal scan of all power connections Tighten loose connections. Check converter & inverter transfer operation. Place critical load on maintenance bypass if applicable Exercise external maintenance bypass breakers, if applicable AC input failure test - battery operation, with customer approval. Test and confirm Maintenance Bypass Switch operability. Place UPS back in service to support critical load. *Annual System Checks (MAJOR)-Battery System: Measure and record all inter-cell and main terminal cable ohmic values. Take apart and clean any connection with ohmic value less than the manufacturer s recommended value or has a value that decreased by more than 20 % below the baseline value. Retorque any connections that are below the battery manufacturer s recommended value. Requires DC breaker to be opened or UPS charger to be off (Contingent upon customer approval). * Includes labor and mobilization. No parts included. *The services performed are designed to meet or exceed IEEE Standard and Battery Manufacturer's Recommendations. Semi Annual Checks (Minor) Check if ambient temperature and humidity is within the correct operating range. Clearances Verify unit has proper clearance for ventilation and service purposes. Installation. Verify the unit is installed in a stable, level and upright position free of vibration. Application Confirm proper UPS application. Location Evaluate the UPS location and determine if it is in accordance with the manual. Visual Inspection Check Structure. Paint- Evaluate for missing paint, unevenness, peeling, cracks and/or dirt. Frame- Evaluate for bends, cracks, rust, dirt, welds, and/or parts alignment Covers- Evaluate for bends, dirt, stability, and/or gaps Accessories- Check caster positions and all labels are applied Assembly Screws are secure- Confirm that all screws are secure Broken or alien parts- Check for broken or alien parts Connectors and wires condition- Evaluate the condition of the connectors and wires Edge guards secure- Confirm that all edge guards are secure Fast-on lugs secure- Confirm that fast-on lugs are secure Wires Route Clearance- Confirm that the wire route clearances are within spec PCB connections- Confirm that the wire route PCB connections are within spec Ratings and settings Dip switch setting- Verify proper dip switch settings for PCBs Unit s rating- Verify proper unit and/or battery cabinet ratings with sales order Post Operation Checks Unit Clean Up Remove all excess dust and/or dirt internally or externally Customer Service Explanation- Prepare and give final report to customer and explain work performed Work Request- Schedule next PM or repair work that may need to be performed does not include replacement parts. Replacement parts & labor are at time & material cost + 15% Conditions All personnel are subject to completing a successful background check prior to being allowed to conduct any work on the premises. Location of Required Services FEMA Thomasville FRC 436 S. Pinetree Blvd. Thomasville, GA. 31792

From Solicitation posted on Jul 02, 2025

The Purpose of this Firm Fixed Price (FFP) Solicitation is to procure Annual Uninterruptable Power Supply (UPS) Inspections, (1) Major PM inspection and (1) Minor PM inspection to ensure that the equipment is in good working condition to maintain clean power to critical loads in the server room at the FEMA Federal Regional Center (FRC) Thomasville, GA Facility. SCOPE OF WORK Annual and Semi-Annual UPS Inspections at FEMA Thomasville FRC UNIT SPECIFICATIONS Make: ABB Model: Series SG Serial Number: P00802820B270R kVA/Capacity: 80KVA SG UPS Type of batteries: VRLA Number of batteries: 40 batteries (1 Cabinet Sprinter next, AH Capacity 87, Runtime 365 Model Number -S12v325fl) Annual System Checks (Major) Thermal scan of all power connections Tighten loose connections. Check converter & inverter transfer operation. Place critical load on maintenance bypass if applicable Exercise external maintenance bypass breakers, if applicable AC input failure test - battery operation, with customer approval. Test and confirm Maintenance Bypass Switch operability. Place UPS back in service to support critical load. *Annual System Checks (MAJOR)-Battery System: Measure and record all inter-cell and main terminal cable ohmic values. Take apart and clean any connection with ohmic value less than the manufacturer s recommended value or has a value that decreased by more than 20 % below the baseline value. Retorque any connections that are below the battery manufacturer s recommended value. Requires DC breaker to be opened or UPS charger to be off (Contingent upon customer approval). * Includes labor and mobilization. No parts included. *The services performed are designed to meet or exceed IEEE Standard and Battery Manufacturer's Recommendations. Semi Annual Checks (Minor) Check if ambient temperature and humidity is within the correct operating range. Clearances Verify unit has proper clearance for ventilation and service purposes. Installation. Verify the unit is installed in a stable, level and upright position free of vibration. Application Confirm proper UPS application. Location Evaluate the UPS location and determine if it is in accordance with the manual. Visual Inspection Check Structure. Paint- Evaluate for missing paint, unevenness, peeling, cracks and/or dirt. Frame- Evaluate for bends, cracks, rust, dirt, welds, and/or parts alignment Covers- Evaluate for bends, dirt, stability, and/or gaps Accessories- Check caster positions and all labels are applied Assembly Screws are secure- Confirm that all screws are secure Broken or alien parts- Check for broken or alien parts Connectors and wires condition- Evaluate the condition of the connectors and wires Edge guards secure- Confirm that all edge guards are secure Fast-on lugs secure- Confirm that fast-on lugs are secure Wires Route Clearance- Confirm that the wire route clearances are within spec PCB connections- Confirm that the wire route PCB connections are within spec Ratings and settings Dip switch setting- Verify proper dip switch settings for PCBs Unit s rating- Verify proper unit and/or battery cabinet ratings with sales order Post Operation Checks Unit Clean Up Remove all excess dust and/or dirt internally or externally Customer Service Explanation- Prepare and give final report to customer and explain work performed Work Request- Schedule next PM or repair work that may need to be performed does not include replacement parts. Replacement parts & labor are at time & material cost + 15% Conditions All personnel are subject to completing a successful background check prior to being allowed to conduct any work on the premises. Location of Required Services FEMA Thomasville FRC 436 S. Pinetree Blvd. Thomasville, GA. 31792

From Solicitation posted on Jul 03, 2025

The Purpose of this Firm Fixed Price (FFP) Solicitation is to procure Annual Uninterruptable Power Supply (UPS) Inspections, (1) Major PM inspection and (1) Minor PM inspection to ensure that the equipment is in good working condition to maintain clean power to critical loads in the server room at the FEMA Federal Regional Center (FRC) Thomasville, GA Facility. SCOPE OF WORK Annual and Semi-Annual UPS Inspections at FEMA Thomasville FRC UNIT SPECIFICATIONS Make: ABB Model: Series SG Serial Number: P00802820B270R kVA/Capacity: 80KVA SG UPS Type of batteries: VRLA Number of batteries: 40 batteries (1 Cabinet Sprinter next, AH Capacity 87, Runtime 365 Model Number -S12v325fl) Annual System Checks (Major) Thermal scan of all power connections Tighten loose connections. Check converter & inverter transfer operation. Place critical load on maintenance bypass if applicable Exercise external maintenance bypass breakers, if applicable AC input failure test - battery operation, with customer approval. Test and confirm Maintenance Bypass Switch operability. Place UPS back in service to support critical load. *Annual System Checks (MAJOR)-Battery System: Measure and record all inter-cell and main terminal cable ohmic values. Take apart and clean any connection with ohmic value less than the manufacturer s recommended value or has a value that decreased by more than 20 % below the baseline value. Retorque any connections that are below the battery manufacturer s recommended value. Requires DC breaker to be opened or UPS charger to be off (Contingent upon customer approval). * Includes labor and mobilization. No parts included. *The services performed are designed to meet or exceed IEEE Standard and Battery Manufacturer's Recommendations. Semi Annual Checks (Minor) Check if ambient temperature and humidity is within the correct operating range. Clearances Verify unit has proper clearance for ventilation and service purposes. Installation. Verify the unit is installed in a stable, level and upright position free of vibration. Application Confirm proper UPS application. Location Evaluate the UPS location and determine if it is in accordance with the manual. Visual Inspection Check Structure. Paint- Evaluate for missing paint, unevenness, peeling, cracks and/or dirt. Frame- Evaluate for bends, cracks, rust, dirt, welds, and/or parts alignment Covers- Evaluate for bends, dirt, stability, and/or gaps Accessories- Check caster positions and all labels are applied Assembly Screws are secure- Confirm that all screws are secure Broken or alien parts- Check for broken or alien parts Connectors and wires condition- Evaluate the condition of the connectors and wires Edge guards secure- Confirm that all edge guards are secure Fast-on lugs secure- Confirm that fast-on lugs are secure Wires Route Clearance- Confirm that the wire route clearances are within spec PCB connections- Confirm that the wire route PCB connections are within spec Ratings and settings Dip switch setting- Verify proper dip switch settings for PCBs Unit s rating- Verify proper unit and/or battery cabinet ratings with sales order Post Operation Checks Unit Clean Up Remove all excess dust and/or dirt internally or externally Customer Service Explanation- Prepare and give final report to customer and explain work performed Work Request- Schedule next PM or repair work that may need to be performed does not include replacement parts. Replacement parts & labor are at time & material cost + 15% Conditions All personnel are subject to completing a successful background check prior to being allowed to conduct any work on the premises. Location of Required Services FEMA Thomasville FRC 436 S. Pinetree Blvd. Thomasville, GA. 31792

From Solicitation posted on Jul 08, 2025

Notice history

3
  1. Solicitation Posted Jul 02, 2025 View
  2. Solicitation Posted Jul 03, 2025
    • Description: Description was updated
  3. Solicitation LATEST Posted Jul 08, 2025
    • Response Deadline: Jul 09, 2025Jul 11, 2025

Details

Solicitation number 70FBR425Q00000153
Notice ID ba356760c2b1436a9131b02cee8ed06b
Notice type Solicitation
Product / Service (PSC) H349
NAICS 541350
Set-aside No Set aside used
Place of performance Thomasville, Georgia
Archive date Jul 12, 2025

Award Information

Not yet awarded

Contacts

primary
Tiffany Young

Email

Phone

secondary
Kimberly Coakley

Email

Phone

Agency

HOMELAND SECURITY, DEPARTMENT OF
FEDERAL EMERGENCY MANAGEMENT AGENCY
REGION 4: EMERGENCY PREPAREDNESS AN

Place of Performance

Thomasville, Georgia 31792
USA

Dates

Posted Jul 08, 2025 1 year ago
Last Updated Aug 06, 2026 1 day ago
Due Jul 11, 2025 1 year ago