C1DA--AE Upgrade Nursing Unit Isolation Rooms & Airflows - 583-25-202 36C25026R0050

Solicitation 36C25026R0050 Copied Notice ID ddd7f746baae48f29ce1c0deaf6c2714 Copied VETERANS AFFAIRS, DEPARTMENT OF — 250-NETWORK CONTRACT OFFICE 10 (36C250)
SAM.gov
Posted
Dec 23, 2025
Deadline
Jan 14, 2026
Set-aside
SDVOSBC
NAICS
541330
PSC
C1DA

Summary

AI-generated · Dec 20, 2025

Upgrade nursing unit isolation rooms and airflow at the VAMC Indianapolis by designating 31 pressure-designated rooms as fixed negative (27 rooms) or fixed positive (4 rooms) spaces, disabling and removing the dual-keyed interface, and removing equipment no longer needed. Ensure operations conform to VA requirements and fire/smoke regulations in normal and epidemic conditions, with clear definitions of pressure differences (negative: at least 0.01 WC, 0.02 WC for double negative; positive: at least 0.01 WC, 0.02 WC for double positive). The A/E will inspect all components affecting pressure balance, identify deficiencies, determine current operation, and design changes to meet current VA standards and industry practice.

The A/E shall prepare plans and specifications to remediate all deficiencies and provide project support through bidding and construction, including construction-period services such as field inspections, submittal reviews, RFIs, and contract-change support with associated cost estimates. Selection will consider professional qualifications, specialized experience, capacity, past performance, local knowledge, and the extent of commitment to employing service-disabled veteran-owned, veteran-owned, and other small businesses as subs, along with other criteria. Submittals must be electronic SF-330 packages; no physical copies, due by the stated closing time.

Description of Requirement: The VAMC, Indianapolis has a requirement to maintain air pressure differentials between some designated patient rooms and the adjoining corridors or spaces. This pressure differential can be either positive, that is, the interior of the patient room has greater air pressure than does the adjoining corridor or space, or negative, that is, the interior of the patient room has a lower air pressure than does the adjoining corridor or space. Currently, some patient rooms are designed to be both positive and negative, selectable by a keyed interface. This dual functionality is no longer permitted under VA regulations so in accordance with the following table, each room shall be designated as either negative or positive; the keyed interface shall be disabled and removed, and the room operating sequence shall only function as indicated in the following table. Any equipment no longer required by this change shall be removed and discarded. At the conclusion of the project there shall be 27 negative pressure only rooms and four positive pressure only rooms. The terms positive and negative pressures shall be defined as follows: A single negative pressure symbol (-) shall mean a minimum negative pressure difference of 0.01 Water Column (WC); a double negative designation (--) shall mean a minimum negative pressure differential of 0.02 WC. A single positive pressure symbol (+) shall mean a minimum positive pressure differential of 0.01 WC. A double positive pressure symbol (++) shall mean a minimum positive pressure differential of 0.02 WC. The A/E shall inspect and review all components of each room that can influence the pressure balance; identify all deficient components; determine how the rooms are operating in their current configuration; determine what changes are required to enable the rooms to operate in conformance with current VA requirements and industry standards under normal conditions, under epidemic conditions, and in compliance with all fire and smoke regulations and requirements. Compliance with all fire and smoke regulations shall include both normal and epidemic conditions. The use of the phrase epidemic mode is defined to mean an operating condition in which all negative pressure rooms maintain design pressure differences and air changes concurrently; AHUs meet the minimum outdoor air and filtration set points, and sequences accommodate extended door-open events. After the A/E presents a list of deficiencies and solutions to the VA; the A/E shall design, in conjunction with the VA, solutions for the identified components and system deficiencies. The A/E shall prepare plans and specifications to remediate all such deficiencies in components and systems and provide project assistance through the bidding and construction phases. The hospital has 31 total pressure designated rooms with four rooms being designated as positive and the remaining 27 are designated as negative pressure rooms. Selection Criteria: (1) Professional qualifications necessary for satisfactory performance of required services. (2) Specialized experience and technical competence in the type of work required, including, where appropriate, experience in energy conservation, pollution prevention, waste reduction, and the use of recovered materials. (3) Capacity to accomplish the work in the required time. (4) Past performance on contracts with Government agencies and private industry in terms of cost control, quality of work, and compliance with performance schedules. (5) Location in the general geographical area of the project and knowledge of the locality of the project; provided, that application of this criterion leaves an appropriate number of qualified firms, given the nature and size of the project. (6) Experience in construction period services to include professional field inspections during the construction period, review of construction submittals, support in answering requests for information during the construction period, and support of construction contract changes to include drafting statements of work, and cost estimates shall be included as an evaluation criterion when construction period services is included in the statement of work for A-E services. (7) The extent to which potential contractors identify and commit to the use of service-disabled veteranowned small businesses, veteran-owned small businesses, and other types of small businesses as subcontractors. SF 330 Submittal Instructions: All interested and capable firms are to submit an electronic SF330 package for review. Physical copies will not be accepted. The SF330s can be submitted to the below email address: luke.turner@va.gov The package must be received and in government control by the closing time/date of this announcement.

From Presolicitation posted on Dec 19, 2025

This posting is to extend the due date for SF 330s, as outlined above. ***END OF POSTING***

From Presolicitation posted on Dec 23, 2025

Notice history

2
  1. Presolicitation Posted Dec 19, 2025 View
  2. Presolicitation LATEST Posted Dec 23, 2025
    • Description: Description was updated
    • Response Deadline: Jan 06, 2026Jan 14, 2026

Details

Solicitation number 36C25026R0050
Notice ID ddd7f746baae48f29ce1c0deaf6c2714
Notice type Presolicitation
Product / Service (PSC) C1DA
NAICS 541330
Archive date Apr 14, 2026

Award Information

Awardees
0

Contacts

primary
Contracting Officer

Luke A. Turner

Email

Phone

Agency

VETERANS AFFAIRS, DEPARTMENT OF
VETERANS AFFAIRS, DEPARTMENT OF
250-NETWORK CONTRACT OFFICE 10 (36C250)

Place of Performance

Richard L. Roudebush VA Medical Center 1481 W. 10th Street
Indianapolis, IN 46202-2803

Dates

Posted Dec 23, 2025 7 months ago
Last Updated Aug 06, 2026 1 day ago
Due Jan 14, 2026 6 months ago