4210--Fire Suppression Service, Testing, Maintenance, Certification Amendment 1 36C25625Q1231
Summary
AI-generated · Aug 24, 2025Fire suppression service contract requires a single vendor to perform testing, maintenance, and certification of all fire suppression systems at designated facilities. The work covers routine inspections and tests (annual, semi-annual, and quarterly as applicable), 5-year certification, standpipe and dry standpipe tests, diesel fire pump testing and related flow tests (hydrants, FDC), hydrostatic tests, internal piping condition checks, and replacement of all fire system gauges. The scope may expand to include future buildings and associated tanks; current in-scope facilities include an energy plant and other projects still in design, with as-builts for new buildings not yet provided. Documentation such as existing drawings and placards for tanks and antifreeze systems will be supplied as needed, and testing outside normal hours is not anticipated beyond 9 PM. proposers may submit Volumes 1 and 2 as separate documents if desired, as long as both are included in the final quote.
The amendments provide Q&A responses and clarifications that expand bid data: past inspection history and copies of recent annual inspection reports are available; information on the existing pump and systems is clarified (pump maker, model, and rated capacity), and the contract’s EP6 weekly or monthly pump tests are not required (weekly diesel pump runs are performed instead). Details address the antifreeze tank size and water storage tank specifications (with attachments referenced), the status of future buildings and their drawings, and confirmation that two proposal volumes can be separate documents. Close-date extension is noted, and bidders should plan to include all requested data, with pricing for known base-year activities and flexibility for unknown future inspections.
This is an amendment to: To update the close date of the solicitation to August 19, 2025 at 15:00.
From Combined Synopsis/Solicitation posted on Aug 11, 2025RFQ 36C25625Q1231 Question and Answer Reponses The purpose of this amendment is to: To reply to all questions that were submitted by the deadline of 08/15/2025 at 3pm CST. Extend the close date of the solicitation to 08-20-2025 at 16:30. Vendor 1 Can you please provide copies of the most recent annual inspection reports for these systems? Answer: Yes, they can be supplied. Canteen/NFS semi-annual fire suppression testing was performed 3/19/2025. Which contract years will the future buildings be completed construction and devices added to this scope of work? Can you please share the fire sprinkler drawings for these buildings so we can get an idea of the added devices? Will inspections of the new above ground and underground water tanks be required under this contract? If so, please provide the drawings for these tanks. Answer: New Energy Plant- September 2025. New OI&T unknown, still in design stage. New building as-builts have not been provided, still under construction and have not been delivered as yet under contract. Above Ground water tank is not designated as fire protection. Both current underground tanks will become fire suppression dedicated. Yes, that is the 1946 as built. When are each of the 5-year certification and testing required? Or when were they last performed? If unknown, will it be acceptable to include pricing in the base year and then move the funding to other years if it becomes known when these inspections will be required? Answer: 5 Year Certification and Testing: last performed in 2020, except for dry standpipe (2024) and gauges (2025) Internal Standpipe flow test (Bldg. 1)-base year Diesel Fire Pump Flow test-base year Fire Hydrant flow GPM test-base year Fire Department Connection (FDC) Hydrostatic test-base year Fire Sprinkler Internal Piping Condition and Obstruction Inspection-base year Replace all fire system gauges, to include negative gauge located on Fire Pump intake impeller-OY-5 Dry Standpipe in Garage- OY-4 The scope of work references quarterly, semi-annual and annual inspections, however it also references the Joint Commission EC 02.03.05 EP6 Weekly or Monthly Fire Pump Tests depending on power supply. Can you please confirm if we should include pricing for EP6? Answer: No, we conduct weekly fire pump runs of the diesel fire pump. Can you provide the fire pump manufacturer and model number? Also, can you confirm the rated flow (gpm)? The solicitation mentions 2,500 gpm in some areas and 1,250 gpm in another area. Please confirm. Answer: PUMP MFG: FAIRBANKS MORSE RATED GPM 1250 RATED PSI 164 MODEL: 6"1825F 150% GPM 1875 150% PSI 156 SERIAL: 04-1152055 SHUTOFF 0 S.O. PSI 175 RATED RPM 1750 PUMP FLANGE SIZE 8 X 6 IMP.DIA. 19.500 What is the approximate size in gallons of the antifreeze system? Provide photo of placard if possible. Answer: See Attachment 1 Can you please provide information on the existing water storage tank? Size (gallons) and construction type. Answer: See Attachment 2 Are there any known inspection and testing activities that will be required to be performed outside of normal working hours? Any specific buildings or floors/rooms in specific buildings? Answer: No fire alarms/testing after 9PM Can you please confirm if Volumes 1 and 2 of the proposal (based on proposal breakdown instructions) can be two separate documents? Answer: They can be two separate documents, but be sure to include both in your final quote/response.
From Combined Synopsis/Solicitation posted on Aug 18, 2025Notice history
2-
Combined Synopsis/Solicitation Posted Aug 11, 2025
-
Combined Synopsis/Solicitation LATEST Posted Aug 18, 2025View changes (3)
- Title: 4210--Fire Suppression Service, Testing, Maintenance, Certification Amendment 1 → 4210--Fire Suppression Service, Testing, Maintenance, Certification Amendment 2
- Description: Description was updated
- Response Deadline: Aug 19, 2025 → Aug 20, 2025
Details
Award Information
Contacts
Contract Specialist
Phone
Agency
Place of Performance
Shreveport, LA 71101