(4) Chiller Coils and Installation 1605C4-25-Q-00051
Summary
AI-generated · Aug 27, 2025Replace four condenser coils on the B-1 Carrier Chiller unit by providing and installing four Carrier 30RB660055 MCHX E-Coated Coil Kits that have failed on circuit A. The chiller is a 2008 model (30RBA13064-517-3), serial 1908Q86121, located at Building 1. Work includes evacuating all R410a from circuit A, testing for contamination, removing the existing coils, installing contractor-provided coils, evacuating the circuit and using nitrogen to test for leaks, recharging the system with refrigerant, and, if introducing new R410a, adding Galgon Easy Seal.
The overall objective of this endeavor is to replace four condenser coils on the B-1 Carrier Chiller unit. This requirement includes the contractor to provide and install four Carrier 30RB660055 MCHX E-Coated Coil Kits that have failed on circuit A of the chiller located at Building 1. The Carrier Chiller is a 2008 Model, Model #: 30RBA13064-517-3, Serial #: 1908Q86121. Evacuating all the R410a refrigerant from the chiller unit s A Circuit and test to make sure there is no contamination in the refrigerant. Remove the existing, failed, condenser coils. Install new, contractor-provided, Carrier coil kits. Vacuum down the A Circuit and charge with nitrogen to test for any leaks. Add refrigerant back into the A Circuit and if new R410a is being introduced into the system, add Galgon Easy Seal.
From Combined Synopsis/Solicitation posted on Jul 16, 2025Notice history
1-
Combined Synopsis/Solicitation LATEST Posted Jul 16, 2025
Details
Award Information
Not yet awarded
Contacts
Phone
Phone
Agency
Place of Performance
USA